Understanding the NLP's Maximum Simultaneous Station Run

Modified on Fri, 15 Nov at 10:21 AM

The NLP supports both 2-Wire (Tucor decoder) and conventional (SERB) output. Refer to your output type for reference. See footnote for Hybrid Configurations (1)


2-Wire


TypeMax Active
NG-Series (All)40(3)
LD-050, LD-100, LD-200(4)10+
LD-400, LD-600(4)
10+
RKLD-050(4) 10+


Conventional


Brand & ModelIn-Rush (mA)Holding (mA)Max Active (Per 1, 24-Output SERB)(2)
Hunter 606800
350
190
4
Rainbird CP/CPF, EFB, PGA, PEB/PESB4101405
Rainbird DV/DVF4502503
Rainbird HV290918
Bermad S-309-2W-24VAC-R2501256
Netafim Series 80220958
K-Rain P30081134302503



(1) For NLPs controlling both Conventional (SERB) & 2-Wire (Decoder) outputs, the maximum simultaneous station run can be found by adding Max Active value for both types. For retrofit customers with NG & legacy decoders, a wire quality test is required to determine max station run if greater than 10. 


(2) Each 24-Station Station Extension Relay Board (SERB) requires a separate transformer, the maximum station run is limited per SERB & by solenoid. For sites with multiple SERBs, the Max Active is valid per each SERB. 


(3) Depending upon sensor count, valve type & wire condition, this number may vary. 


(4) All retrofit customers looking to run > 10 stations simultaneously perform a wire quality test. Failure to complete this test may result issues with decoder operation. 